| 2022-07-27 10:36:36 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT THE COMPLETE PRODUCT APPROVALS AND/OR |
| | EVALUATION REPORTS FOR THE FLOOD VENT MODEL 1540-530 |
| | AND TRIM AND SLEEVE KIT 1540-531-12. |
| | |
| | 2) THE BOOK AND PAGE NUMBER IN SECTION A3 OF THE |
| | ELEVATION CERTIFICATE DOES NOT MATCH THE ONES ON THE |
| | SURVEY DRAWINGS THAT WERE SUBMITTED. OUR RECORDS SHOW |
| | THAT THE PLATS ARE RECORDED IN BOOK 130, PAGE 178. |
| | PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 3) THE BUILDING DIAGRAM NUMBER IN SECTION A7 OF THE |
| | ELEVATION CERTIFICATE SHOULD BE 1A FOR THE GARAGES. |
| | THEY ARE NOT RAISED SLAB ON GRADE PER NFIP ELEVATION |
| | CERTIFICATE INSTRUCTIONS PAGE 7 OF 9. |
| | |
| | 4) THE INFORMATION THAT IS ENTERED IN SECTION A9 OF THE |
| | ELEVATION CERTIFICATE SHOULD BE ENTERED IN SECTION A8. |
| | THIS IS A DETACHED GARAGE AND SECTION A9 IS FOR GARAGES |
| | THAT ARE ATTACHED TO ANOTHER BUILDING. IN SECTION A4 IT |
| | SHOULD BE NOTED THAT THIS IS A DETACHED GARAGE. |
| | |
| | 5) THE SQUARE FOOTAGE OF THE GARAGE SHOULD BE 2,154 |
| | SQUARE FEET BASED ON THE MEASUREMENTS TO THE OUTSIDE |
| | WALL AS SHOWN ON THE SURVEY. NFIP ELEVATION CERTIFICATE |
| | INSTRUCTIONS ITEM A8.A. |
| | |
| | 6) THE TOP OF BOTTOM FLOOR ENTERED IN SECTION C2. A) IS |
| | 15.53 FEET AND THE SURVEY HAS 15.00 FEET. PLEASE VERIFY |
| | AND MAKE NECESSARY CORRECTIONS. FBC 107.2.1 |
| | |
| | 7) SUBMIT A PHOTOGRAPH OF THE RIGHT SIDE OF THE GARAGE |
| | THAT PROVIDES A BETTER VIEW OF THE FLOOD VENTS ON THAT |
| | SIDE. FBC 107.2.1 |
| | |
| | 8) PROVIDE A SITE PLAN THAT CLEARLY IDENTIFIES EACH |
| | GARAGE BY A NUMBER THAT CORRESPONDS WITH THE ELEVATION |
| | CERTIFICATE. FBC 107.2.1 |