| 2022-06-24 14:57:56 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22060728 |
| | 6/24/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 6: PROVIDE TDH CALCULATIONS FOR THE POOL AND |
| | THE SPA- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & |
| | R4501.7.2 & R4501.7.3 FBC RES. |
| | |
| | 2) SHEET 6: THE PERMIT APPLICATION INDICATES "PER PLAN" |
| | SO IT ASSUMED THAT THE POOL, SPA, AND POND SHOWN ON THE |
| | PLAN WILL BE PERMITTED TOGETHER. THE PLANS SHOW THE |
| | SAME RECIRCULATION PUMP USED FOR BOTH THE POOL AND SPA |
| | HOWEVER THE FLOW RATE CALCULATIONS SHOWN ON THE SHEET 6 |
| | APPEAR TO BE FOR THE POOL ONLY. PLEASE REFER TO YOUR |
| | SPECIFICATIONS INFORMATION ON SHEET 2 WHICH LISTS THE |
| | SPA VOLUME AT 1,926 GALLONS AND 4309 GALLONS (POND |
| | GALLONS NOT PROVIDED). PLEASE REVISE THE FLOW RATE |
| | CALULATIONS TO INCLUDE THE SPA AND MARK UP THE PUMP |
| | CURVE ON THE SHEET TO SHOW THE TDH AND FLOW RATE OF THE |
| | SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & |
| | R4501.7.2 & R4501.7.3 FBC RES. |
| | |
| | 3) THE POOL, SPA, AND POND ARE BEING CONSTRUCTED IN A |
| | FLOOD HAZARD ZONE. PLEASE PROVIDE HYDROSTATIC RELIEF |
| | DEVICES TO BE LOCATED AT THE LOW POINTS OF THE MAIN |
| | DRAINS- SEC. R4501.21.4 FBC RES. |
| | |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | RECIRCULATION EQUIPMENT- PUMP, FILTER, CHLORINATOR- AND |
| | THE UNBLOCKABLE DRAIN- SECS. R4501.6.2 & R4501.6.6 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |