2022-06-24 14:57:561ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060728
 6/24/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 6: PROVIDE TDH CALCULATIONS FOR THE POOL AND
 THE SPA- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES.
  
 2) SHEET 6: THE PERMIT APPLICATION INDICATES "PER PLAN"
 SO IT ASSUMED THAT THE POOL, SPA, AND POND SHOWN ON THE
 PLAN WILL BE PERMITTED TOGETHER. THE PLANS SHOW THE
 SAME RECIRCULATION PUMP USED FOR BOTH THE POOL AND SPA
 HOWEVER THE FLOW RATE CALCULATIONS SHOWN ON THE SHEET 6
 APPEAR TO BE FOR THE POOL ONLY. PLEASE REFER TO YOUR
 SPECIFICATIONS INFORMATION ON SHEET 2 WHICH LISTS THE
 SPA VOLUME AT 1,926 GALLONS AND 4309 GALLONS (POND
 GALLONS NOT PROVIDED). PLEASE REVISE THE FLOW RATE
 CALULATIONS TO INCLUDE THE SPA AND MARK UP THE PUMP
 CURVE ON THE SHEET TO SHOW THE TDH AND FLOW RATE OF THE
 SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES.
  
 3) THE POOL, SPA, AND POND ARE BEING CONSTRUCTED IN A
 FLOOD HAZARD ZONE. PLEASE PROVIDE HYDROSTATIC RELIEF
 DEVICES TO BE LOCATED AT THE LOW POINTS OF THE MAIN
 DRAINS- SEC. R4501.21.4 FBC RES.
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 RECIRCULATION EQUIPMENT- PUMP, FILTER, CHLORINATOR- AND
 THE UNBLOCKABLE DRAIN- SECS. R4501.6.2 & R4501.6.6 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  