| Plan Review Notes For Permit 22060717 |
| Permit Number |
22060717 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-29 12:41:50 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22060717 | | | 7/29/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS 1 & 3: POOL CAPACITY IS LISTED AT 9920 | | | GALLONS ON SHEET 1 BUT THE SYSTEM FLOW CALCS ON SHEET 3 | | | INDICATE 13,460 GALLONS- PLEASE CORRECT THE PLANS- SEC. | | | 107.2.1 WPB. | | | | | | 2) SHEET 1 & 3: THE TDH CALCULATIONS DO NOT SHOW THE | | | LENGTHS OF THE SUCTION AND PRESSURE PIPING- | | | ANSI/APSP/ICC-7 2013. | | | | | | 3) SHEET 3: PLEASE PROVIDE POOL EQUIPMENT ANCHORING | | | DETAILS- TYPES AND SIZES OF ANCHOR BOLTS OR TAPCONS- | | | SEC. R4501.22 FBC RES. | | | | | | 4) SHEET 5: REFER TO SEC. R4501.6.1 FBC RES AND SHOW | | | THE CURRENT YEAR EDITIONS OF THE DESIGN STANDARDS IN | | | EFFECT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|