| 2022-08-22 11:15:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION THAT THIS IS REVISION OF |
| | MASTER PERMIT # 21061851, WHICH DOESN'T SHOW |
| | CANOPY/AWNING WORK. |
| | |
| | PER NFPA 1 |
| | 1.14 PLAN REVIEW. |
| | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| | |
| | PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE |
| | REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS, |
| | ARE LOCATED. |
| | |
| | |
| | 1A) THERE IS NO SITE PLAN INDICATING THE LOCATIONS OF |
| | EACH PROPOSED CANOPY/AWNING. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4. |
| | |
| | PLEASE PROVIDE A DETAILED SITE PLAN. |
| | |
| | |
| | 1B) THERE IS NO INDICATIONS OF THE DIMENSIONS OF EACH |
| | CANOPY. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE PROVIDE DETAILED DIMENSIONS OF EACH |
| | CANOPY/AWNING. |
| | |
| | 1C) THERE IS NO INDICATION OF FLAME RETARDANT |
| | CERTIFICATION. |
| | |
| | PER NFPA 101 |
| | |
| | 11.9.1.6 FLAME PROPAGATION PERFORMANCE. |
| | 11.9.1.6.1 ALL MEMBRANE STRUCTURE FABRIC SHALL MEET THE |
| | FLAME PROPAGA TION PERFORMANCE CRITERIA CONTAINED IN |
| | TEST METHOD 2 OF NFPA 701. |
| | 11.9.1.6.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE |
| | THAT THE FABRIC |
| | MATERIALS HAVE THE REQUIRED FLAME PROPAGATION |
| | PERFORMANCE: |
| | (1) THE AUTHORITY HAVING JURISDICTION SHALL REQUIRE A |
| | CERTIFICATE OR OTHER |
| | EVIDENCE OF ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO |
| | THE AUTHOR ITY HAVING JURISDICTION. |
| | (2) THE AUTHORITY HAVING JURISDICTION SHALL REQUIRE A |
| | REPORT OF TESTS |
| | MADE BY OTHER INSPECTION AUTHORITIES OR ORGANIZATIONS |
| | ACCEPTABLE |
| | TO THE AUTHORITY HAVING JURISDICTION. |
| | |
| | PLEASE PROVIDE. |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |