| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| | FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| | WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK, |
| | DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES |
| | THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE |
| | GOING TO THE SANITARY AND NOT TO THE GREASE WASTE. |
| | PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF |
| | GREASE WASTE AND SANITARY WASTE. |
| | |
| | 2. 2020 FPC - 607.1.1 - PLEASE INDICATE THAT THE HOT |
| | WATER IS IN COMPLIANCE WITH 607.1.1. A THERMOSTATIC |
| | MIXING DEVICE SHALL BE INSTALLED ON THE HOT WATER |
| | DELIVERY SYSTEM. IF THERE IS NOT ONE, IT SHALL BE |
| | ADDED. THIS REQUIREMENT FOR HOT WATER DELIVERY |
| | PROTECTION IS IN ADDITION TO THE REQUIREMENTS FOR |
| | TEMPERED WATER DELIVERY REQUIRED BY 607.1.2. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |