2022-08-02 13:17:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 WOOD FLOORS ARE PROPOSED OVER AN UNDERLAYMENT WHICH IS
 NOT CLEAR.
  
 STC TEST FOR PROFLEX MSC 90 WAS SUBMITTED (QUARRY TILE,
 8" SLAB) - NOT OK
 IIC TEST FOR PROFLEX SUPERSIM 90 (TILE, 6" SLAB) - TEST
 OK
 STC TEST FOR PROFLEX SUPERSIM 90 PARTIAL TEST SUBMITTED
 - TEST OK (WE CAN PROVIDE COMPLETE TEST)
 NO FLAME SPREAD SUBMITTED
  
 IT IS SUGGESTED THAT YOU EITHER CONTACT PROFLEX TO SEE
 IF THEY HAVE A FLAME SPREAD TEST FOR SUPERSIM90 WITH A
 COMBUSTIBLE FLOOR, OR CONSIDER PROFLEX LV200 AS PROFLEX
 HAS RECOMMENDED THIS PRODUCT IN THE PAST AND WE HAVE
 THE THREE TEST REPORTS ON FILE. IF YOU ELECT TO TAKE
 THIS OPTION, PLEASE NOTE THAT I DO NOT TAKE INTO
 ACCOUNT QUALITY, SUITABILITY, PRICE, ETC., SIMPLY CODE
 COMPLIANCE AND AVAILABILITY OF THE TEST REPORTS.
  
 SEE PREVIOUS REVIEW FOR CODE REFERENCES.