Plan Review Notes
Plan Review Notes For Permit 22060638
Permit Number 22060638
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-27 12:07:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF AN EXIT STAIRWELL ROOF
 REPAIR AND VENT WITH SEVREAL BACKUP AND BID DOCUMENTS,
 HOWEVER, THARE ARE NO PLAN SHEETS SUBMITTED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE CONSTRUCTION
 PLAN SHEETS.
  
  
 1A) THE REPLACEMENT VENT APPEARS TO BE RELATED TO
 EITHER THE STAIRWELL PRESSURIZATION SYSTEM OR SMOKE
 EVACUATION SYSTEM.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE DETAILS WITH A SEQUENCE OF OPERATIONS.
  
 ALL RELATED TESTING SHALL BE COMPLETED BY A QUALFIED
 3RD PARTY WITH A REPORT OF COMPLAINCE SUBMITTED PRIOR
 TO FIRE INSPECTION.
  
  
 2) PLEASE PROVIDE A LIFE SAFETY EVALAUTION FOR THE
 PROPOSED INDCATING THE PROTECTION OF THE EGRESS, EGRESS
 SAFETY, AND WHAT MEASURES ARE PROPOSED TO MAINTAINING
 THE EGRESS PER # 1A).
  
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL