| 2022-06-23 16:43:21 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22060637 |
| | 6/23/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE POTABLE WATER BACKFLOW PREVENTER, THE IRRIGATION |
| | SYSTEM AND IRRIGATION BACKFLOW PREVENTER, THE SWIMMING |
| | POOL, AND THE CABANA- SECS. 105.1 & 107.2.1 WPB. |
| | 2) SHEET P1.1: PLEASE SHOW KEYNOTE 3, 4, 6, 7, 8, 9, 10 |
| | LOCATIONS ON THE PLAN- SEC. 107.2.1 WPB. |
| | 3) P1.2: THE PLAN APPEARS TO SHOW A BATHTUB IN THE |
| | SHOWER SPACE IN HER BATHROOM. PROVIDE AN ENLARGED |
| | DETAIL SHOWING THE WIDTH AND DEPTH OF THE SHOWER PAN |
| | AND PAN INSTALLATION DETAILS- SECS. P2709.1 & P2709.2 |
| | FBC RES. |
| | 4) P1.1 & P3.1: INDICATE HOW DRAINAGE FROM THE ICE |
| | MAKERS WILL BE CONVEYED TO THE SANITARY SYSTEM- SEC. |
| | P2601.2 FBC RES. |
| | 5) P3.1: PROVIDE THE TEXT NOTES FOR KEYNOTES 1-6, A & B |
| | SHOWN ON THE RISER- SEC. 107.2.1 WPB. |
| | 6) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN |
| | AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC |
| | RES, PLUMBING FIXTURES, APPLIANCES, PIPING ETC. SHALL |
| | BE INSTALLED AT OR ABOVE THE ELEVATION REQUIRED IN |
| | SECTION R322.2 FBC RES. PLEASE PLACE NOTES AND DETAILS |
| | ON THE PLANS SHOWING COMPLIANCE WITH R322.1.7: |
| | PROTECTION OF WATER SUPPLY AND SANITARY SEWAGE SYSTEMS |
| | NEW WATER SUPPLY AND SANITARY PIPING SYSTEMS. NEW AND |
| | REPLACEMENT WATER SUPPLY SYSTEMS SHALL BE DESIGNED TO |
| | MINIMIZE OR ELIMINATE INFILTRATION OF FLOOD WATERS INTO |
| | THE SYSTEMS IN ACCORDANCE WITH THE PLUMBING PROVISIONS |
| | OF THIS CODE. NEW AND REPLACEMENT SANITARY SEWAGE |
| | SYSTEMS SHALL BE DESIGNED TO MINIMIZE OR ELIMINATE |
| | INFILTRATION OF FLOODWATERS INTO SYSTEMS AND DISCHARGES |
| | FROM SYSTEMS INTO FLOODWATERS IN ACCORDANCE WITH THE |
| | PLUMBING PROVISIONS OF THIS CODE AND IN ACCORDANCE WITH |
| | CHAPTER 64E-6, FLORIDA ADMINISTRATIVE CODE, STANDARDS |
| | FOR ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEMS. SEE |
| | ALSO SECTION 7.3 ASCE 24-14. |
| | 6) C-1 SISTERN 1 & 2- SEC. 107.2.1 WPB: A) PROVIDE |
| | ENLARGED INSTALLATION DETAILS INCLUDING FLOOD WATER |
| | ANCHORING DETAILS. B) INDICATE THE CAPACITIES OF THE |
| | TANKS AND SIZING CALCULATIONS. C) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |