| 2022-09-08 17:46:21 | PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE | | | PRE-CONSTRUCTION ELEVATION CERTIFICATE. | | | - ITEM A1 CORRECT THE OWNER'S NAME TO AQUANTIS GROUP | | | LLC. | | | - ITEM A3 CORRECT PALM BEACH COMPANY'S TO PALM BEACH | | | COUNTY'S. | | | - ITEM A7 SHOULD BE 1B. | | | - ITEM A9 A) THE SQFT OF THE GARAGE IS SPECIFIED AS 488 | | | SQFT. THIS IS DIFFERENT FROM THE FLOOR PLAN A.1.1 (BLDG | | | DATA= 552 SQFT) AND THE SITE PLAN A.0.1 ( FLOOD VENT | | | CALCULATIONS= 546 SQFT). THE INSTRUCTIONS FOR | | | COMPLETING THE ELEVATION CERTIFICATE FROM FEMA FOR ITEM | | | A9 A) SAYS TO TAKE THE MEASUREMENTS FROM THE OUTSIDE OF | | | THE GARAGE. PLEASE VERIFY THE SQUARE FEET OF THE | | | GARAGE. | | | - ITEM A9 B) SHOULD BE 4. | | | -ITEM A9 C) SHOULD BE THE NET AREA OF THE SMART VENTS. | | | THE 200 SQFT COVERAGE PER SQFT SHOULD BE EXPLAINED IN | | | THE COMMENTS FOR SECTION D. | | | - ITEM A9 D) SHOULD BE MARKED YES FOR ENGINEERED FLOOD | | | OPENINGS. | | | -ITEM B4 HAS THE WRONG MAP/PANEL NUMBER. IT SHOULD BE | | | 12099C 0583. | | | - SECTION D COMMENTS SHOULD SPECIFY (4) SMART VENTS | | | MODEL # 1540-520 WITH 200 SQFT OF COVERAGE FOR EACH FOR | | | A TOTAL OF 800 SQFT. | | | - REMOVE THE FLOOR PLAN FROM THE PHOTO SECTION. | | | - A SEPARATE ELEVATION CERTIFICATE IS REQUIRED FOR THE | | | POOL CABANA BECAUSE IT IS A SEPARATE STRUCTURE. |
|