| 2022-06-24 07:45:18 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22060637 |
| | 6/23/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS |
| | AND NOTE THAT INSTALLATIONS OF THE GAS PIPING AND |
| | GAS-FIRED APPLIANCES CAN BE UNDER A SEPARATE PERMIT BY |
| | REQUEST. |
| | |
| | 1) P1.1. & P3.2: PLEASE NOTE THAT SEPARATE PERMITS ARE |
| | REQUIRED FOR THE GENERATOR AND THE POOL HEATER- SEC. |
| | 105.1 & 107.2.1 WPB. |
| | 2) P1.1 & P3.2- FLOOD ZONE HAZARD: THE PROPERTY APPEARS |
| | TO BE IN AN AE FLOOD HAZARD ZONE. ACCORDING TO SECTION |
| | R322.1.6 FBC RES THE GAS PIPING AND GAS-FIRED |
| | APPLIANCES AND EQUIPMENT SHALL BE INSTALLED AT OR ABOVE |
| | THE ELEVATION REQUIRED IN SECTION R322.2 FBC RES. |
| | PLEASE PROVIDE NOTES AND DETAILS VERIFYING COMPLIANCE |
| | FOR THE WATER HEATERS, POOL HEATERS, GENERATOR, FIRE |
| | PITS, AND BBQ GRILL |
| | 3) P1.1 & P3.2: PROVIDE CLEARANCE DISTANCE MEASUREMENTS |
| | FOR THE GAS WATER HEATERS TO THE WINDOWS- SECS. G2427.8 |
| | & G2448.1 FBC RES. |
| | 4) P3.2 GAS RISER: PROVIDE THE CORRECT PIPE SIZING |
| | TABLES FOR THE NATURAL GAS SYSTEM. THE TABLES SHOWN ON |
| | THE PLAN- TABLE 16.1 NFPA 58 AND TABLE 402.4(28) FBC FG |
| | ARE FOR LP GAS- SECS. G2413.3 & G2413.4 FBC RES, & |
| | 402.3 & 402.4 FBC FG. PLEASE INCLUDE THE TABLES FOR THE |
| | 2.0 PSI PE AND SCHEDULE 40 METALLIC, AND THE LOW |
| | PRESSURE PE, SCHEDULE 40 METALLIC, AND ANY OTHER LO |
| | PRESSURE PIPING NOT IDENTIFIED ON THE RISER. |
| | 5) P3.2: THE RISER APPEARS TO SHOW A 1-INCH SCHEDULE 40 |
| | METALLIC SUPPLY PIPE FROM THE METER TO THE 2-INCH PE |
| | WHICH WOULD BE UNDERSIZED PER TABLE G2413.4(2) FBC RES |
| | & 402.4(5) FBC FG. BASED ON THE TABLE A 2-INCH PIPE IS |
| | REQUIRED. |
| | 6) P3.2: SHOW THE TYPES AND SIZES OF SUPPLY PIPING FROM |
| | PE TO THE POOL HEATER, GENERATOR, BBQ GRILL, |
| | FIREPLACES, GAS WATER HEATERS- SECS.G2413.3 & G2413.4 |
| | FBC RES & 402.3 & 402.4 FBC FG. |
| | 7) P3.2: INDICATE THE MAKES AND MODELS OF REGULATORS TO |
| | BE INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS, |
| | AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION |
| | G2421.2 FBC RES. |
| | 8) P3.2: FIRE PITS ARE INCORRECTLY LABELED AS FIRE |
| | PLACES ON THE RISER- SEC. 107.2.1 WPB. |
| | 9) P3.2: PROVIDE MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUALS FOR THE VENTLESS FIREPLACES, BBQ |
| | GRILL, TANKLESS WATER HEATER, AND THE OUTDOOR FIRE |
| | PITS- SECS G2445.1, G2447.1, G2448.1, G2454.1 FBC RES. |
| | 10) P3.2: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED |
| | TO THE VENTLESS FIREPLACES AND PROVIDE CALCULATIONS- |
| | SEC. G22407.1 FBC RES. |
| | 11) P3.2: PROVIDE AN ELEVATION VIEW DRAWING OF THE BBQ |
| | GRILL SHOWING CLEARANCES TO COMBUSTIBLES AND OVERHEAD |
| | CONSTRUCTION PER THE MANUFACTURER'S RECOMMENDATIONS. |
| | PLEASE NOTE THAT INSTALLATION OF AN EXHAUST HOOD AND |
| | DUCT SYSTEM MAY BE REQUIRED BASED ON MANUFACTURER'S |
| | INSTALLATION GUIDELINES- SECS. G2408.1 & G2447.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |