| 2023-05-10 10:28:32 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22060604 |
| | 5/10/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE REVIEW THE BUILDING REVIEW COMMENTS DATED |
| | 5/9/23. A COMPLETE REVIEW OF THE PLUMBING AND |
| | ACCESSIBLE BATHROOM FIXTURES CANNOT BE ACCOMPLISHED AT |
| | THIS TIME UNTIL THE BUILDING COMMENTS HAVE BEEN |
| | ADDRESSED- SEC. 107.2.1 WPB. |
| | |
| | 2) P01 & P02: PLEASE SHOW THE CENTERLINES OF THE TOILET |
| | PAPER DISPENSERS MEASURED FROM THE FRONTS OF THE WATER |
| | CLOSETS- SECTION AND FIGURE 604.7 FBC ACC. |
| | |
| | 3) P01 & P02: PLEASE PROVIDE FBC ACC ACCESSIBLE SHOWER |
| | DETAILS INCLUDING; |
| | A) DIMENSIONS OF THE SHOWERS- SECTIONS 608.2.1 & |
| | 608.2.2. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWERS- SECTIONS 608.2.1 & 608.2.2 |
| | C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWERS- SECTIONS 608.3.1 AND |
| | 608.3.2 |
| | D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1 AND 608.5.2. |
| | E) LOCATIONS OF AND MOUNTING DETAILS FOR ACCESSIBLE |
| | SHOWER SEATS- SECTIONS 610.3 & 610.3.2. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |