2023-05-09 10:36:18WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22060604
 ADD: 7001 S DIXIE HWY
 CONT: TYG CONSTRUCTION SOLUTIONS
 TEL: 561-891-5124
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MAY 09TH/ 2023
 ACTION: DENIED
 I TRIED REACHING OUT TO THE DESIGNER OF RECORD
 ALEXANDER ROJAS PE # 75704 BY PHONE 561-891-5124. THE
 RECORDING STATED THE MAILBOX IS FULL. SENT THEN MSM
 TELEPHONE NUMBER. I DON'T BELIEVE THE DESIGNER OF
 RECORD HAS REVIEWED SECTION 405.1- 450.1.3OF THE 2020
 FBC-BUILDING CODE THAT STATES: STATE LICENSED NURSING
 HOMES ARE EXEMPT FROM USING THE FLORIDA EXISTING
 BUILDING CODE, THEY ARE REQUIRED TO MEET THE
 REQUIREMENTS OF THE CURRENT BUILDING CODE AS IN NEW
 CONSTRUCTION AND GUIDELINES RESIDENTIAL HEALTH, CARE
 AND SUPPORT FACILITIES AS WELL AS FLORIDA
 ADMINISTRATIVE CODE:
 RULE 59A-4.1265, EMERGENCY ENVIRONMENTAL CONTROL FOR
 NURSING HOMES
 TIER II REPORTING INFORMATION FOR FUEL STORAGE AT
 NURSING HOMES & ASSISTED LIVING FACILITIES
 EMERGENCY POWER PLAN (536KB PDF)
  
 1A) 3RD ROUND COMMENTS. THE ENGINEER HAS ONLY PARTLY
 RESPONDED PARTLY TO COMMENT # 1 WITH IDENTIFYING THE
 OCCUPANCY TYPE.
 THE RESPONSE NOTES INDICATE THIS FACILITY IS A NURSING
 HOME. IN THE 2020 FBC-BUILDING CODE SECTION308.4
 INSTITUTIONAL GROUP I-2 INCLUDES NURSING HOMES, WHAT
 THE DESIGNER WILL NEED TO INDICATE IF CLASSIFY
 OCCUPANCY CONDITIONS UNDER 308.4.1. CONDITION 1 OR
 CONDITION 2. NO ARCHITECTURAL PLANS WERE SUBMITTED TO
 SHOW COMPLIANCE WITH SECTION 450 & 407 NURSING HOMES OF
 THE 2020 FBC-BUILDING AND GUIDELINES RESIDENTIAL
 HEALTH, CARE AND SUPPORT FACILITIES AS WELL AS FLORIDA
 ADMINISTRATIVE CODE:
 RULE 59A-4.1265, EMERGENCY ENVIRONMENTAL CONTROL FOR
 NURSING HOMES
 TIER II REPORTING INFORMATION FOR FUEL STORAGE AT
 NURSING HOMES & ASSISTED LIVING FACILITIES
 EMERGENCY POWER PLAN (536KB PDF)
 GUIDELINES RESIDENTIAL HEALTH, CARE & SUPPORT
 FACILITIES SECTIONS:
  
 3.1.2 RESIDENTIAL AREAS
  
 3.2 SPECIFIC REQUIREMENTS FOR NURSING HOMES PAGES 125-
 141.
  
 1ST ROUND OF COMMENTS. THE TITLE BLOCK OF THE PLANS
 STATE THIS REMODEL IS A CHANGE OF OCCUPANCY TO A
 ASSISTED LIVING FACILITY, NO ARCHITECTURAL PLANS WERE
 SUBMITTED TO SHOW COMPLIANCE WITH SECTION 464 OF THE
 2020 FBC-BUILDING AND AGENCY OF HEALTH CARE
 ADMINISTRATION (AHCA) RULE 58A-5, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 400 PART III, FLORIDA
 STATUTES.
 2020FBC-ACCESSIBILITY CODE SECTION 223.3 LONG TERM CARE
 FACILITIES. 805. 1-5.
  
 1B) 3RD REQUEST. PLEASE REVIEW ALL OF THE LISTED
 DOCUMENTS FOR NURSING HOME DESIGN INCLUDING EMERGENCY
 ENVIRONMENTAL CONTROLS.
  
 1ST ROUND OF COMMENTS. THERE IS AN INTERIOR DEMOLITION
 PLAN WITH THE REMOVAL OF ALL WINDOWS, AND ONLY A
 PARTIAL 1ST FLOOR MECHANICAL PLAN. THE 2020
 FBC-BUILDING CODE SECTION 1203.5 & 1203.5.1 BOTH
 REQUIRE NATURAL VENTILATION OR SECTION 1204.1 INTERIOR
 SPACES INTENDED FOR HUMAN OCCUPANCY SHALL PROVIDE
 EITHER ACTIVE OR PASSIVE SPACE HEATING. NO FLOOR PLAN
 WAS SUBMITTED FOR BUILDING REVIEW.
  
 2) 3RD REQUEST. THERE IS AN INTERIOR DEMOLITION PLAN
 WITH THE REMOVAL OF ALL WINDOWS, NO BUILDING FLOOR PLAN
 WAS SUBMITTED, WITH THE REMOVAL OF ALL WINDOWS & SHEETS
 E1 & E2 NEITHER SHOW ANY INTERIOR LIGHTING IN ANY ROOMS
 EXCEPT FOR THE BATHROOMS PLEASE REVIEW THE 2020
 FBC-BUILDING CODE 1205.1, 1205.2 & 1205.3.
  
 3)3RD REQUEST. THE DEMO FLOOR PLAN SHOWS 23 UNITS LESS
 ONE NO NUMBER 13 SO THERE IS 22 LIVING UNITS. THE 2020
 FBC-ACCESSIBILITY CODE TABLE 224.2 WILL REQUIRE ONE
 GUEST BATHROOM TO HAVE MOBILITY FEATURES AND SECTION
 806 TRANSIENT LODGING GUEST ROOMS. THERE ARE NO
 BUILDING OR ARCHITECTURAL SHEETS PROVIDED IN THIS
 REVIEW.
 THE ELECTRICAL SHEET HAS A 3D MOCK UP OF A RESTROOM BUT
 NOT THE ACTUAL DESIGN OF THE BATHROOMS, ALSO SMALLER
 THAN 1/8 INCH SCALE. 107.2.1.3. QUALITY OF PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH SCALE ON
 SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 4) 3RD REQUEST. IF PHASING INDICATE ON THE PLANS, PHASE
 2 UNDER SEPARATE PERMIT.
 1ST ROUND OF COMMENTS. THE DEMO PLAN SHOWS WORK TO BE
 ACCOMPLISHED ON THE 2ND FLOOR, BUT THE PLANS ARE SILENT
 AS TO VERTICAL ACCESSIBILITY. 2020 FBC-ACCESSIBILITY
 CODE SECTION 201.1.1 VERTICAL ACCESSIBILITY AND
 SECTION:
 4A) FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2020 ACCESSIBILITY CODE.
  
 4B) 202.4.2 ACCESSIBILITY FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF THE ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREAS FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COST. IN
 CHOOSING WHICH ELEMENTS TO PROVIDE, PRIORITY SHOULD BE
 GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE GREATEST
 ACCESS, IN THE FOLLOWING ORDER: (I) AN ACCESSIBLE
 ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA;
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM; (IV) ACCESSIBLE TELEPHONES:
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND (VI) WHEN
 POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS
 PARKING, STORAGE, AND ALARMS.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION. PLEASE NOTE WITH THE LACK OF
 INFORMATION FOR THIS REVIEW, SUBSEQUENT REMARKS MAYBE
 MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  