2022-10-11 07:52:162ND REVIEW FMC
 PERMIT: 22060604
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS I-2 OCCUPANCY MUST MEET THE VENTILATION
 REQUIREMENTS OF ASHRAE 170-2017. FMC 407
  
 2) THIS MEANS THE PREVIOUS COMMENT NUMBER 3 MUST ALSO
 BE ADDRESSED. SEE BELOW:
  
 3) SINCE YOU HAVE DESIGNED THE MECHANICAL SYSTEMS AS
 MINI SPLITS, SHOW THE NATURAL VENTILATION CALCULATIONS
 FOR EACH SPACE OF THIS BUILDING. FMC 402 AND 407.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  