Plan Review Notes
Plan Review Notes For Permit 22060604
Permit Number 22060604
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-08 17:04:541ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22060604
 8/8/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-01 & D-01: PLEASE SUBMIT PLUMBING PLANS AND
 SPECIFICATIONS FOR THE BATHROOM RENOVATIONS- SECS
 107.2.1, 107.3.5.1.1 & 107.3.5.1.3 WPB. PLEASE INCLUDE:
 A) SCOPE OF WORK OUTLINE.
 B) FIXTURE SCHEDULE.
 C) RISER DRAWINGS FOR ALTERATIONS TO THE EXISTING WATER
 SUPPLY AND SANITARY DRAIN AND VENT PIPES.
 D) SOURCES OF HOT AND TEMPERED WATER TO FIXTURES.
 E) ENLARGED FLOOR PLANS SHOWING COMPLIANCE WITH SEC.
 202.3 FBC-2020 ACCESSIBILITY CODE. PLEASE NOTE SITE
 SPECIFIC DRAWINGS ARE REQUIRED. THE GENERIC ACCESSIBLE
 BATHROOM DRAWING ON SHEETS E-01 AND E-02 DOES NOT MATCH
 THE BATHROOM LAYOUTS SHOWN ON THE FLOOR PLAN AND ALSO
 HAS MISSING ACCESSBILITY COMPLIANCE DETAILS INCLUDING:
  
 * HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 * HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 * LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB BARS
 FOR THE WATER CLOSETS- SECTIONS 604.5 & 609.4, FIGURES
 604.
 * CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 * KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 SHOWERS:
 * CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWERS- SECTIONS 608.2.1 & 608.2.2
 * LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB BARS
 FOR THE ACCESSIBLE SHOWERS- SECTIONS 608.3.1 AND
 608.3.2
 * LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1 AND 608.5.2.
 * SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 * LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 &
 610.3.2.
  
 NOTES:
 1) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH THE
 FBC EXISTING BUILDING CODE. REFER TO SEC. 301 AND
 INDICATE THE CHOSEN COMPLIANCE PATH ON SHEET A-01.
 COMPLIANCE UNDER LEVEL I, II OR III PATHS MAY BE
 SUBJECT TO ADDITIONAL FBC PLUMBING AND ACCESSIBILITY
 COMPLIANCE REQUIRMENTS.
  
 2) PLEASE REFER TO FLORIDA ADMINISTRATIVE CODE (FAC)
 RULE 59-A-36.025- EMERGENCY ENVIRONMNETAL CONTROL FOR
 ASSISTED LIVING FACILITIES. THE RULE, WHICH REQUIRES AN
 ALTERNATE POWER SOURCE (GENERATOR) TO ENSURE AMBIENT
 TEMPERATURE CONTROL AND VENTILATION SHALL BE MAINTAINED
 FOR A SPECIFIC PERIOD TIME IN THE EVENT OF POWER LOSS.
 PLEASE REVIEW THE RULE AND VERIFY THE NEW AND EXISITNG
 HVAC AND POWER SYSTEMS ARE CONNECTED TO THE EMERGENCY
 GENERATOR, AND MEET THE CRITERIA IN ACCORDANCE WITH
 ITEM (1) AND SUB-SECTIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  