| 2022-08-08 16:14:26 | 1ST REVIEW FMC |
| | PERMIT: 22060604 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE IS ONLY ONE SHEET SUBMITTED FOR THE |
| | MECHANICAL-M-01. PLEASE PROVIDE A COMPLETE MECHANICAL |
| | SET OF DRAWINGS FOR THIS STRUCTURE INCLUDING ALL ROOMS |
| | AND THE MECHANICAL SYSTEM LOCATION FOR EACH, ALSO |
| | INCLUDE THE 2ND STORY ROOMS AND CORRIDOR. |
| | |
| | 2) SHOW THE OCCUPANCY CLASSIFICATION OF THIS BUILDING. |
| | FMC 401.2 |
| | 401.2 VENTILATION REQUIRED. EVERY OCCUPIED SPACE SHALL |
| | BE VENTILATED BY NATURAL MEANS IN ACCORDANCE WITH |
| | SECTION 402 OR BY MECHANICAL MEANS IN ACCORDANCE WITH |
| | SECTION 403. WHERE THE AIR INFILTRATION RATE IN A |
| | DWELLING UNIT IS LESS THAN 3 AIR CHANGES PER HOUR WHEN |
| | TESTED WITH A BLOWER DOOR AT A PRESSURE |
| | OF 0.2-INCH WATER COLUMN (50 PA) IN ACCORDANCE WITH |
| | SECTION R402.4.1.2 OF THE FLORIDA BUILDING CODE, ENERGY |
| | CONSERVATION, THE DWELLING UNIT SHALL BE VENTILATED BY |
| | MECHANICAL MEANS IN ACCORDANCE WITH SECTION 403. |
| | AMBULATORY CARE FACILITIES AND GROUP I-2 OCCUPANCIES |
| | SHALL BE VENTILATED BY MECHANICAL MEANS IN ACCORDANCE |
| | WITH SECTION 407. |
| | |
| | 3) SINCE YOU HAVE DESIGNED THE MECHANICAL SYSTEMS AS |
| | MINI SPLITS, SHOW THE NATURAL VENTILATION CALCULATIONS |
| | FOR EACH SPACE OF THIS BUILDING. FMC 402 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |