2022-08-08 16:14:261ST REVIEW FMC
 PERMIT: 22060604
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS ONLY ONE SHEET SUBMITTED FOR THE
 MECHANICAL-M-01. PLEASE PROVIDE A COMPLETE MECHANICAL
 SET OF DRAWINGS FOR THIS STRUCTURE INCLUDING ALL ROOMS
 AND THE MECHANICAL SYSTEM LOCATION FOR EACH, ALSO
 INCLUDE THE 2ND STORY ROOMS AND CORRIDOR.
  
 2) SHOW THE OCCUPANCY CLASSIFICATION OF THIS BUILDING.
 FMC 401.2
 401.2 VENTILATION REQUIRED. EVERY OCCUPIED SPACE SHALL
 BE VENTILATED BY NATURAL MEANS IN ACCORDANCE WITH
 SECTION 402 OR BY MECHANICAL MEANS IN ACCORDANCE WITH
 SECTION 403. WHERE THE AIR INFILTRATION RATE IN A
 DWELLING UNIT IS LESS THAN 3 AIR CHANGES PER HOUR WHEN
 TESTED WITH A BLOWER DOOR AT A PRESSURE
 OF 0.2-INCH WATER COLUMN (50 PA) IN ACCORDANCE WITH
 SECTION R402.4.1.2 OF THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION, THE DWELLING UNIT SHALL BE VENTILATED BY
 MECHANICAL MEANS IN ACCORDANCE WITH SECTION 403.
 AMBULATORY CARE FACILITIES AND GROUP I-2 OCCUPANCIES
 SHALL BE VENTILATED BY MECHANICAL MEANS IN ACCORDANCE
 WITH SECTION 407.
  
 3) SINCE YOU HAVE DESIGNED THE MECHANICAL SYSTEMS AS
 MINI SPLITS, SHOW THE NATURAL VENTILATION CALCULATIONS
 FOR EACH SPACE OF THIS BUILDING. FMC 402
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  