Plan Review Notes
Plan Review Notes For Permit 22060604
Permit Number 22060604
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-11 13:32:36THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 -OCCUPANCY REQUIRES A CHANGE OF USE PERMIT MEETING ALL
 REQUIREMENTS FOR A NEW RESIDENTIAL BOARD AND CARE
 FACILITY, NFPA 101 CH.33
  
 -33.2.3.4.1 FIRE ALARM SYSTEMS. A MANUAL FIRE ALARM
 SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 9.6, UNLESS THE PROVISIONS OF 33.2.3.4.1.1 OR
 33.2.3.4.1.2 ARE MET.
  
 -33.2.3.4.1.1 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED
 WHERE INTERCONNECTED SMOKE ALARMS COMPLYING WITH NFPA
 101 CH.33.2.3.4.3 AND NOT LESS THAN ONE MANUAL FIRE
 ALARM BOX PER FLOOR ARRANGED TO CONTINUOUSLY SOUND THE
 SMOKE DETECTOR ALARMS ARE PROVIDED.
  
 - 33.2.3.5.3 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED,
 FOR EITHER TOTAL OR PARTIAL BUILDING COVERAGE, ALL OF
 THE FOLLOWING
 REQUIREMENTS SHALL BE MET:
 (1) THE SYSTEM SHALL BE IN ACCORDANCE WITH SECTION 9.7
 AND SHALL
 INITIATE THE FIRE ALARM SYSTEM IN ACCORDANCE WITH
 33.2.3.4.1,
 AS MODIFIED BY 33.2.3.5.3.1 THROUGH 33.2.3.5.3.6.
 (2) THE ADEQUACY OF THE WATER SUPPLY SHALL BE
 DOCUMENTED TO
 THE AUTHORITY HAVING JURISDICTION.
 33.2.3.5.3.1* IN PROMPT EVACUATION CAPABILITY
 FACILITIES, ALL OF
 THE FOLLOWING SHALL APPLY:
 (1) AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 NFPA 13D, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS
 IN ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED
 HOMES, SHALL BE PERMITTED.
 (2) AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN
 CLOSETS NOT
 EXCEEDING 24 FT2 (2.2 M2) AND IN BATHROOMS NOT
 EXCEEDING
 55 FT2 (5.1 M2), PROVIDED THAT SUCH SPACES ARE FINISHED
 WITH LATH AND PLASTER OR MATERIALS PROVIDING A
 15-MINUTE
 THERMAL BARRIER.
  
  
  
 33.2.3.5.3.4 IN PROMPT AND SLOW EVACUATION CAPABILITY
 FACILITIES
 IN BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 EXISTING RESIDENTIAL BOARD AND CARE OCCUPANCIES 101?307
 2015 EDITION
 ACCORDANCE WITH NFPA13R, STANDARD FOR THE INSTALLATION
 OF SPRINKLER
 SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE
 PERMITTED.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  