Plan Review Notes
Plan Review Notes For Permit 22060604
Permit Number 22060604
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-16 15:22:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22060604
 ADD: 7001 S DIXIE HWY
 CONT: TYG CONSTRUCTION SOLUTIONS
 TEL: 561-891-5124
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 16TH/ 2022
 ACTION: DENIED
  
 1A) THE TITLE BLOCK OF THE PLANS STATE THIS REMODEL IS
 A CHANGE OF OCCUPANCY TO A ASSISTED LIVING FACILITY, NO
 ARCHITECURAL PLANS WERE SUBMITTED TO SHOW COMPLIANCE
 WITH SECTION 464 OF THE 2020 FBC-BUILDING AND AGENCY OF
 HEALTH CARE ADMINISTRATION (AHCA) RULE 58A-5, FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 400 PART III, FLORIDA
 STATUTES.
  
 1B) THERE IS AN INTERIOR DEMOLITION PLAN WITH THE
 REMOVAL OF ALL WINDOWS, AND ONLY A PARTIAL 1ST FLOOR
 MECHANICAL PLAN. THE 2020 FBC-BUILDING CODE SECTION
 1203.5 & 1203.5.1 BOTH REQUIRE NATURAL VENTILATION OR
 SECTION 1204.1 INTERIOR SPACES INTENDED FOR HUMAN
 OCCUPANCY SHALL PROVIDE EITHER ACTIVE OR PASSIVE SPACE
 HEATING. NO FLOOR PLAN WAS SUBMITTED FOR BUILDING
 REVIEW.
  
 2) THERE IS AN INTERIOR DEMOLITION PLAN WITH THE
 REMOVAL OF ALL WINDOWS, NO BUILDING FLOOR PLAN WAS
 SUBMITTED, WITH THE REMOVAL OF ALL WINDOWS & SHEETS E1
 & E2 NEITHER SHOW ANY INTERIOR LIGHTING IN ANY ROOMS
 EXCEPT FOR THE BATHROOMS PLEASE REVIEW THE 2020
 FBC-BUILDING CODE 1205.1, 1205.2 & 1205.3.
  
 3) THE DEMO FLOOR PLAN SHOWS 23 UNITS LESS ONE NO
 NUMBER 13 SO THERE IS 22 LIVING UNITS. THE 2020
 FBC-ACCESSIBILITY CODE TABLE 224.2 WILL REQUIRE ONE
 GUEST BATHROOM TO HAVE MOBILITY FEATURES AND SECTION
 806 TRANSIENT LODGING GUEST ROOMS. THERE ARE NO
 BUILDING OR ARCHITECTURAL SHEETS PROVIDED IN THIS
 REVIEW.
 THE ELECTRICAL SHEET HAS A 3D MOCK UP OF A RESTROOM BUT
 NOT THE ACTUAL DESIGN OF THE BATHROOMS, ALSO SMALLER
 THAN 1/8 INCH SCALE. 107.2.1.3. QUALITY OF PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH SCALE ON
 SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 4) THE DEMO PLAN SHOWS WORK TO BE ACCOMPLISHED ON THE
 2ND FLOOR, BUT THE PLANS ARE SILENT AS TO VERTICAL
 ACCESSIBILITY. 2020 FBC-ACCESSIBILITY CODE SECTION
 201.1.1 VERTICAL ACCESSIBILITY AND SECTION:
 4A) FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2020 ACCESSIBILITY CODE.
  
 4B) 202.4.2 ACCESSIBILITY FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF THE ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREAS FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COST. IN
 CHOOSING WHICH ELEMENTS TO PROVIDE, PRIORITY SHOULD BE
 GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE GREATEST
 ACCESS, IN THE FOLLOWING ORDER: (I) AN ACCESSIBLE
 ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA;
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM; (IV) ACCESSIBLE TELEPHONES:
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND (VI) WHEN
 POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS
 PARKING, STORAGE, AND ALARMS.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.PLEASE NOTE WITH THE LACK OF
 INFORMATION FOR THIS REVIEW, SUBSEQUENT REMARKS MAYBE
 MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  