Plan Review Notes
Plan Review Notes For Permit 22060570
Permit Number 22060570
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-07-26 11:06:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NOW AN INDICATION OF THE CARPETING BEING
 INSTALLED BUT NO SPEC SHEET FOR THE PROPOSED CARPET.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.2.2* INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7 UNDER ANY OF
 THE FOLLOWING CONDITIONS:
 (1) WHERE FLOOR FINISH REQUIREMENTS ARE SPECIFIED
 ELSEWHERE IN THE
 CODE
 (2) WHERE THE FIRE PERFORMANCE OF THE FLOOR FINISH
 CANNOT BE DEMONSTRATED TO BE EQUIVALENT TO FLOOR
 FINISHES WITH A CRITICAL RADIANT FLUX
 OF AT LEAST 0.1 W/CM2
  
 10.2.7.1* CARPET AND CARPET-LIKE INTERIOR FLOOR
 FINISHES SHALL COMPLY
 WITH ASTM D2859, STANDARD TEST METHOD FOR IGNITION
 CHARACTERISTICS
 OF FINISHED TEXTILE FLOOR COVERING MATERIALS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED CARPET
 INDICATING THE FIRE BEHAVIOR RATING IN COMPLIANCE WITH
 THE CODE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  