| Plan Review Notes For Permit 22060560 |
| Permit Number |
22060560 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-03 14:05:52 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE DISTANCE FROM THE GENERATOR EXHAUST | | | TO ANY BUILDING OPENINGS - FBC R303.5.1 INTAKE | | | OPENINGS. | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. |
|