Plan Review Notes
Plan Review Notes For Permit 22060558
Permit Number 22060558
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-07-27 13:14:32EXCEPT FOR THE SUBMITTAL OF THE FLOOR PLAN, THE
 PREVIOUS COMMENTS FOR FIRE NOT BEEN ADDRESSED.
  
 IS THIS A REVISON OF A PREVIOUS PERMIT?
  
 WHAT IS THE TYPE OF TILE/FINISHED FLOOING? IF LAMINATE
 TYPE FLOORING PROVIDE THE PRODUCT NAME AND SPEC SHEET
 SHOWING THE FLAME RATING.
  
 IF CERAMIC, MARBLE, ETC, PLEASE INDICAATE IT ON THE
 FLOOR PALN, NO SPEC SHEET IS NEEDED.
  
 THE PREVIOUS FIRE COMMENTS ARE SUBMITTED BELOW WITH THE
 FLLOR PLAN COMMENT REMOVED.
  
 *******************************************************
 *************************************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF ON THE APPLICATION OF TILE
 CHANGE.
  
 THAT IS A VERY GENRAL DESCRIPTION WITH NO DETAILS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE A BETTER DECRIPTIVE OF THE PROPOSED
 SCOPE OF WORK,
  
  
  
 2) IN THE BACK UP DOCUMENTS THERE IS A SPEC SHEET FOR
 THE FLOOR UNDERLAYMENT WITH THE CITY OF WPBCH PERMIT #
 21120939, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE
 ACTUAL PROPOSED TILE FLOORING.
  
 TILE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 DIIFFERENT TYPES AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 IF THE PROPOSED TILE FLOORING IS PORCELAIN/CERAMIC
 TILE, NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC
 SHEETS WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 TILE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2A) IS THIS SUBMITTAL FOR A CHANGE OF FLOORING TYPE?
  
 IF SO, A REVISION APPLICATION IS REQUIRED WITH
 INDICATIONS AS NOTE ABOVE.
  
  
  
 3) PROVIDED
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]