| Plan Review Notes For Permit 22060554 |
| Permit Number |
22060554 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-15 14:04:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE SUBMITTED PLAN SHEET IS THE IDENTICAL PLAN SHEET | | | SUBMITTED FOR PERMIT # 22060349 THAT WAS REJECTED WITH | | | THE COMMENTS BELOW. | | | | | | THIS PERMIT IS BEING REJECTED FOR THE SAME REASON. | | | | | | | | | | | | 1) THERE IS NO NOTIFICATION DEVICES WITH THE RESTROOMS | | | & ELECTRIC ROOM. | | | | | | PER NFPA 72, CH 18 AND NFPA 101 CH 9 | | | | | | PLEASE CORRECT OR PROVIDE A DETAILED NARRATIVE AND SHOW | | | THE LOCATION OF THESE EXISTING DEVICES ON THE | | | RESUBMITTED PLAN SHEET. | | | | | | | | | 1A) PLEASE PROVIDE CLARITY AS TO WHAT SPECIFIC WORK IS | | | BEING DONE FOR EACH SUITE/FLOOR AREA & PERMIT NUMBERS. | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER | | | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE | | | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|