Plan Review Notes
Plan Review Notes For Permit 22060550
Permit Number 22060550
Review Stop E
Sequence Number 1
Notes
Date Text
2022-06-23 14:57:14ELECTRIC REVIEW FAILED
 1) PLEASE SEE NOTES IN SIGNATURE REVIEW
 2) PLEASE PROVIDE PLANS AND DETAILS AS TO THE
 RECONFIGURED WIRING IN CEILING AREAS. FBC 107.2
 3) PLEASE DETAIL THE RECEPTACLE ON KITCHEN ISLAND AS
 REQUIRED PER NEC 210.52 (C)(2)
 4) PLEASE PROVIDE DETAILS FOR ALL NEW WIRING TO COMPLY
 WITH THE FOLLOWING NEC REQUIREMENTS
 NEC 210.8 GFCI PROTECTION,
 NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION,
 NEC 210.52 RECEPTACLE SPACING,
 NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES,
 NEC 250.140 GROUNDING
 AND SMOKE/CARBON ALARMS AS PER FBC R 314
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  