| 2022-06-23 14:57:14 | ELECTRIC REVIEW FAILED | | | 1) PLEASE SEE NOTES IN SIGNATURE REVIEW | | | 2) PLEASE PROVIDE PLANS AND DETAILS AS TO THE | | | RECONFIGURED WIRING IN CEILING AREAS. FBC 107.2 | | | 3) PLEASE DETAIL THE RECEPTACLE ON KITCHEN ISLAND AS | | | REQUIRED PER NEC 210.52 (C)(2) | | | 4) PLEASE PROVIDE DETAILS FOR ALL NEW WIRING TO COMPLY | | | WITH THE FOLLOWING NEC REQUIREMENTS | | | NEC 210.8 GFCI PROTECTION, | | | NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION, | | | NEC 210.52 RECEPTACLE SPACING, | | | NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT | | | RECEPTACLES, | | | NEC 250.140 GROUNDING | | | AND SMOKE/CARBON ALARMS AS PER FBC R 314 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|