| Plan Review Notes For Permit 22060498 |
| Permit Number |
22060498 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-14 11:33:33 | 06/14/22 FAILED - PER CITY CODE, MECHANICAL EQUIPMENT | | | CANNOT PROTRUDE MORE THAN 4 FT INTO ANY SETBACK .THE | | | PROPOSED POOL EQUIPMENT ENCROACHES TOO FAR INTO THE | | | REAR SETBACK OF 12.5 FEET. IT MUST BE SETBACK AT LEAST | | | 8.5 FEET FROM THE REAR PROPERTY LINE. | | | | | | ADITIONALLY, PLEASE SHOW THE LOCATION OF THE PROPOSED | | | FENCE ENCLOSURE ON THE POOL PLAN. | | | | | | THE PERMIT APPLICATION ALSO MENTIONS A DECK BUT THIS IS | | | NOT SHOWN ON THE POOL PLAN. THIS IS FINE BUT IT MEANS | | | THAT A DECK WILL NOT BE PERMITTED UNDER THIS PERMIT. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|