2022-07-19 17:53:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 4501.17.1.9, A POOL ALARM THAT CONFORMS TO
 ASTM F2208-07 IS PROPOSED. ASTM F2208-2014 IS REQUIRED.
 PLEASE PROPOSE AN ALARM THAT COMPLIES; UPLOAD A NEW
 SPEC SHEET.
  
  