Plan Review Notes
Plan Review Notes For Permit 22060481
Permit Number 22060481
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-28 15:35:09ACCORDING TO AREA CALCULATIONS ON SHEET A2 THE NEW
 OFFICE MEZZANINE IS 2,093 SQ FT. NOTE 700 ON SHEET M301
 INDICATES THAT THE OLD AHUIS TO BE REMOVED AND REPLACED
 WITH THE NEW UNIT, THIS NEW UNIT IS TO SERVE BOTH THE
 EXISTING OFFICE AREA AND THE NEW OFFICE MEZZANINE.
 THERE IS NO INDICATION OF THE SQUARE FOOTAGE OF THE 1ST
 FLOOR OFFICES. THE ENERGY CALCULATIONS SUBITTED IS FOR
 THE NEW OFFICE MEZZANINE ONLY. IF THIS NEW UNIT IS TO
 REPLACE THE UNIT THAT WAS CONDITIONING THE 1ST FLOOR
 OFFICES THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 SHOULD INCLUDE THE EXISTING 1ST FLOOR OFFICE AREA IN
 THE CALCULATIONS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved