2022-08-25 13:56:48ELECTRIC REVIEW REQUIRES RESUBMIT
 1) PLEASE DETAIL THE REQUIRED FLOOR RECEPTACLE IN THE
 CONFERENCE ROOM AS PER NEC 210.71(A)(B)(2)
 2) PLEASE DETAIL GFI PROTECTION FOR ALL SINGLE PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND AND LESS LOCATED
 IN KITCHENS OTHER THAN DWELLING UNITS AS PER PLEASE
 INCLUDE 240 VOLT CIRCUITS AS THE Y ARE LESS THAN 150
 VOLTS TO GROUND NEC 210.8(B)(2)
 3) PLEASE PROVIDE A NOTE STATING THAT FIRE ALARM WIRING
 TO DUCT SMOKE DETECTOR REQUIRES A SEPARATE PERMIT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  