| Plan Review Notes For Permit 22060446 |
| Permit Number |
22060446 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-01 09:16:05 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PROVIDE ALL PRODUCT APPROVALS FOR | | | WINDOWS, DOORS, AND ROOFING MATERIALS TO BE USED. | | | | | | FBC B 107.3.4.1, IF THE INTENTION IS TO DEFER THE | | | PRODUCT APPROVALS, PLEASE PROVIDE LIST ON PLANS OF | | | THESE PRODUCTS THAT WILL BE DEFERRED. THESE PRODUCTS | | | CAN NOT BE INSTALLED UNTIL THE PRODUCT APPROVALS HAVE | | | BEEN SUBMITTED WITH DESIGNER OF RECORDS REVIEW STAMP. |
|