| Plan Review Notes For Permit 22060435 |
| Permit Number |
22060435 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-10 15:26:43 | 1ST REVIEW FMC | | | PERMIT: 22060435 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS CONVERSION. | | | FEC 101.5.1.1.2 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS CONVERSION. | | | | | | 3) THE DRYER EXHAUST DUCT MUST BE A MINIMUM OF 28 GA. | | | FRC M1502.4.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | HELPFUL LINKS: | | | WEBSITE FORMS | | | AIR CONDITIONING LIKE FOR LIKE CHANGE OUT FORM | | | | | | | | | YOU CAN CHECK STATUS ON THE WEBSITE: | | | | | | GO TO LINK: | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/PER | | | MITS | | | CLICK ON WHAT IS THE STATUS OF MY PERMIT? | | | |
|