| Plan Review Notes For Permit 22060424 |
| Permit Number |
22060424 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-27 09:36:12 | CLOUD ON MARKUP INDICATES PROPOSED LOCATION FOR FIRE | | | DEPARTMENT CONNECTION. | | | | | | PER NFPA 24, CH.5 | | | 5.9.5 LOCATION AND SIGNAGE. | | | 5.9.5.1* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED | | | AT THE | | | NEAREST POINT OF FIRE DEPARTMENT APPARATUS | | | ACCESSIBILITY OR AT A | | | LOCATION APPROVED BY THE AUTHORITY HAVING JURISDICTION. | | | 5.9.5.2* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED | | | AND ARRANGED | | | SO THAT HOSE LINES CAN BE ATTACHED TO THE INLETS | | | WITHOUT | | | INTERFERENCE. | | | | | | THIS LOCATIION NOT APPROVED FOR FDC, FDC SHALL BE | | | VISIBLE FROM STREET AND EASILY ACCESSIBLE BY APPARATUS. | | | | | | RELOCATE FDC TO NORTH (TAMARIND) AS PREVIOUSLY APPROVED | | | OR SOUTH (BANYAN) FOR ACCESSIBILITY AND VISIBILITY. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|