Plan Review Notes
Plan Review Notes For Permit 22060424
Permit Number 22060424
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-06-27 09:36:12CLOUD ON MARKUP INDICATES PROPOSED LOCATION FOR FIRE
 DEPARTMENT CONNECTION.
  
 PER NFPA 24, CH.5
 5.9.5 LOCATION AND SIGNAGE.
 5.9.5.1* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 AT THE
 NEAREST POINT OF FIRE DEPARTMENT APPARATUS
 ACCESSIBILITY OR AT A
 LOCATION APPROVED BY THE AUTHORITY HAVING JURISDICTION.
 5.9.5.2* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 AND ARRANGED
 SO THAT HOSE LINES CAN BE ATTACHED TO THE INLETS
 WITHOUT
 INTERFERENCE.
  
 THIS LOCATIION NOT APPROVED FOR FDC, FDC SHALL BE
 VISIBLE FROM STREET AND EASILY ACCESSIBLE BY APPARATUS.
  
 RELOCATE FDC TO NORTH (TAMARIND) AS PREVIOUSLY APPROVED
 OR SOUTH (BANYAN) FOR ACCESSIBILITY AND VISIBILITY.
  