| 2022-06-09 14:56:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF AN INFILL OF AN EXTERIOR |
| | DOOR; HOWEVER, THERE IS NO INDICATION OF THE |
| | CONSTRUCTION FEATURES OF THE NEW WALL OR/AND IF THE |
| | EXISTING DOOR IS TO REMAIN ON THE EXTERIOR. |
| | |
| | PER NFPA |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE PROVIDE DETAILS OF THE INTERIOR WALL. |
| | |
| | SHOULD THE EXTERIOR DOOR REMAIN, A SIGN IS REQUIRED TO |
| | BE POSTED ON THE DOOR "NO ENTRY THIS DOOR" OR EQUAL, SO |
| | THAT FF'S KNOW THEY CAN NOT ENTER THAT DOOR IN AN |
| | EMERGENCY. |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED NOTE ON THE NEW |
| | PLAN SHEET. |
| | |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION OF RECONFIGURATION OF THE |
| | KITCHEN AREA; HOWEVER, THE SCOPE OF WORK SHEET DOES NOT |
| | INDICATE FLOORING. |
| | |
| | PER NFPA |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE PROVIDE FLOORING DETAILS. |
| | |
| | |
| | |
| | 2A) SHOULD THERE BE PROPOSED NEW FLOORING A FLOOR |
| | UNDERLAYMENT AND FLOOR MATERIAL/FINISH/TYPE SHOULD BE |
| | SUBMITTED WITH SPECIFICATIONS SHEETS THAT INDICATE |
| | MEETING THE REQUIREMENTS PER NFPA' |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| | CLASSIFICATION. |
| | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| | FINISHES SHALL |
| | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| | IGNITION |
| | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| | MATERIALS. |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| | THE CLASSES SPECIFIED |
| | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| | CRITICAL RADIANT FLUX |
| | REQUIREMENTS. |
| | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED |
| | BY THE TEST DESCRIBED IN 10.2.7.3. |
| | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.22 W/CM2, BUT LESS |
| | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | |
| | |
| | IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL |
| | STONE TILE, CONCRETE TILES, SPEC SHEETS FOR THE FLOOR |
| | FINISH WOULD NOT BE REQUIRED. |
| | |
| | PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |