Plan Review Notes
Plan Review Notes For Permit 22060386
Permit Number 22060386
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-19 08:33:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO SHOW DISTANCE FROM PROPOSED SKYLIGHT
 TO THE PROPERTY LINE. THIS IS NOT PERMITTED WITHIN 4'
 OF THE COMMON 2 HOUR TOWNHOUSE WALL, FBC R 302.2.
  
 2. INDICATE ON THE PRODUCT APPROVAL WHICH OF THE 11
 SKYLIGHT OPTIONS IS PROPOSED, FBC R 301.
  
 3. REVISE PLAN TO SHOW ROOF PITCH AND MEAN ROOF HEIGHT,
 FBC R 301. WE WILL DETERMINE DESIGN PRESSURES FOR YOU
 BUT THIS INFORMATION IS REQUIRED.
  
 4. FBC R 301, FBC 107, THE PRODUCT APPROVAL IS TO
 INCLUDE THE COVER SHEET, EVALUATION REPORT, AND
 INSTALLATION INSTRUCTIONS. A 54 PAGE DOCUMENT WAS
 UPLOADED. IT APPEARS THAT NOT ALL PAGES PERTAIN TO THIS
 INSTALLATION. PLEASE RETAIN ALL GENERAL INFORMATION
 PAGES AND PAGES THAT APPLY TO THE PROPOSED SKYLIGHT,
 REMOVE SHEETS THAT DO NOT APPLY. I TOOK A QUICK GLANCE
 AT THE 54 PAGES AND I DID NOT SEE EVALUATION
 INFORMATION (SPECIFICALLY, WIND DESIGN LIMITATIONS).
 BEFORE RESUBMITTING PLEASE CONFIRM ALL REQUIRED
 INFORMATION IS SUBMITTED. THIS SHOULD UPLOADED AS ONE
 PDF.
  
  
  