| Plan Review Notes For Permit 22060386 |
| Permit Number |
22060386 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-19 08:33:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. REVISE PLAN TO SHOW DISTANCE FROM PROPOSED SKYLIGHT | | | TO THE PROPERTY LINE. THIS IS NOT PERMITTED WITHIN 4' | | | OF THE COMMON 2 HOUR TOWNHOUSE WALL, FBC R 302.2. | | | | | | 2. INDICATE ON THE PRODUCT APPROVAL WHICH OF THE 11 | | | SKYLIGHT OPTIONS IS PROPOSED, FBC R 301. | | | | | | 3. REVISE PLAN TO SHOW ROOF PITCH AND MEAN ROOF HEIGHT, | | | FBC R 301. WE WILL DETERMINE DESIGN PRESSURES FOR YOU | | | BUT THIS INFORMATION IS REQUIRED. | | | | | | 4. FBC R 301, FBC 107, THE PRODUCT APPROVAL IS TO | | | INCLUDE THE COVER SHEET, EVALUATION REPORT, AND | | | INSTALLATION INSTRUCTIONS. A 54 PAGE DOCUMENT WAS | | | UPLOADED. IT APPEARS THAT NOT ALL PAGES PERTAIN TO THIS | | | INSTALLATION. PLEASE RETAIN ALL GENERAL INFORMATION | | | PAGES AND PAGES THAT APPLY TO THE PROPOSED SKYLIGHT, | | | REMOVE SHEETS THAT DO NOT APPLY. I TOOK A QUICK GLANCE | | | AT THE 54 PAGES AND I DID NOT SEE EVALUATION | | | INFORMATION (SPECIFICALLY, WIND DESIGN LIMITATIONS). | | | BEFORE RESUBMITTING PLEASE CONFIRM ALL REQUIRED | | | INFORMATION IS SUBMITTED. THIS SHOULD UPLOADED AS ONE | | | PDF. | | | | | | | | | |
|