Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-13 11:23:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO NOTIFICATION DEVICES WITH THE RESTROOMS
 & ELECTRIC ROOM.
  
 PER NFPA 72, CH 18 AND NFPA 101 CH 9
  
 PLEASE CORRECT OR PROVIDE A DETAILED NARRATIVE AND SHOW
 THE LOCATION OF THESE EXISTING DEVICES ON THE
 RESUBMITTED PLAN SHEET.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL