| Plan Review Notes For Permit 22060314 |
| Permit Number |
22060314 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-21 13:03:55 | 1ST REVIEW FMC | | | PERMIT: 22060314 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A0.01 STATES THE SCOPE OF WORK AS: PROVIDE NEW | | | INTERIOR TENANT BUILD-OUT INCLUDING MECHANICAL, PLEASE | | | PROVIDE A MECHANICAL SCOPE OF WORK AS THE MECHANICAL | | | DRAWING INDICATES EVERYTHING TO BE EXISTING. FBC | | | 107.2.1 | | | | | | 2) PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE OF | | | SPACE INSIDE THIS NEWLY RENOVATED TENANT SPACE. FMC | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 3) THE OUTSIDE AIR CALCULATIONS IS REFERENCING A | | | PREVIOUS EDITION OF THE MECHANICAL CODE, PLEASE UPDATE | | | THIS TO THE CURRENT 7TH EDITION 2020 MECHANICAL CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|