| Plan Review Notes For Permit 22060301 |
| Permit Number |
22060301 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-12-13 08:55:33 | 1) SHEET M.0: THE OUTDOOR AIR SUMMARY TABLE SPECIFIES | | | 1160 CFMS OF OUTDOOR AIR IS REQUIRED. THE EXISTING | | | ROOFTOP SCHEDULE SPECIFIES THAT EACH OF THE 3 RTUS WILL | | | SUPPLY 290 CFMS, WHICH IS ONLY 870 CFMS. PROVIDE THE | | | REQUIRED OUTDOOR AIR FOR THE SPACE. FMC TABLE 403.3.1.1 | | | | | | 2) I DO NOT SEE THE SPECIFICATIONS ASKED FOR IN COMMENT | | | 3 OF 2ND REVIEW CYCLE. PROVIDE DOCUMENTATION THAT SHOWS | | | THE FABRIC DUCT IS LISTED AND LABELED IN COMPLIANCE | | | WITH UL 2518. FMC 603.17 | | | |
|