| 2022-09-30 06:28:45 | 1ST REVIEW FMC |
| | PERMIT: 22060301 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND ATTEMPT: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS FOR THE OCCUPANCY FOR THESE 2 NEW RTU???S. |
| | FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 2) SHEET M-1 SHOWS THE DUCT SMOKE DETECTOR LOCATION AS |
| | BEING IN THE RETURN DUCT. PLEASE SHOW THE DUCT SMOKE |
| | DETECTORS AS BEING LOCATED IN THE SUPPLY DUCT. FMC |
| | 606.2.1 |
| | |
| | 606.2.1 TO PREVENT THE RECIRCULATION OF DANGEROUS |
| | QUANTITIES OF SMOKE, A DETECTOR APPROVED FOR AIR DUCT |
| | USE SHALL BE INSTALLED ON THE SUPPLY SIDE OF |
| | AIR-HANDLING SYSTEMS AS REQUIRED BY NFPA 90A, STANDARD |
| | FOR THE INSTALLATION OF AIR CONDITIONING AND |
| | VENTILATING SYSTEMS. SMOKE DETECTORS LISTED FOR USE IN |
| | AIR DISTRIBUTION SYSTEMS SHALL BE |
| | LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE |
| | CAPACITY GREATER THAN 2000 CUBIC FEET PER MINUTE. |
| | |
| | 3) PROVIDE SPECS ON THE FABRIC DUCT. INCLUDE |
| | DOCUMENTATION THAT THIS PRODUCT IS LISTED AND LABELED |
| | IN COMPLIANCE WITH UL 2518. FMC 603.17 |
| | |
| | 4) THE DESIGNER OF THE MECHANICAL SYSTEM, BEAU CHANT C. |
| | GALLO MUST SHOW THAT THEIR DIGITAL SIGNATURE HAS BEEN |
| | 3RD PARTY VERIFIED. FS 471/481 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |