| 2022-08-01 10:18:17 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22060290 1001 WINDSOR AVE |
| | |
| | 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE |
| | DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC. |
| | R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE |
| | HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR |
| | HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS |
| | CLEAR OPENINGS. |
| | |
| | 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO |
| | COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING |
| | SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4 |
| | INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC. |
| | R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| | NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| | SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| | EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| | REQUIREMENTS. |
| | REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND |
| | NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL |
| | SECTION ON SHEET 4. |
| | |
| | 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION |
| | CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT |
| | SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON |
| | SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC. |
| | R806 FBC-RESIDENTIAL. |
| | |
| | 4- NORTH ARROW ORIENTATION SHOWN ON ALL PLANS SUBMITTED |
| | IS INCORRECT. SEE SURVEY AND REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)VENTED ALUMINUM SOFFIT SPECIFIED ON THE TYPICAL WALL |
| | SECTION. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- ENERGY CALCULATIONS SUBMITTED: |
| | A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE |
| | 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME |
| | SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL" |
| | INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF |
| | SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C)DUCT TESTING IS REQUIRED. REVISE INFORMATION ON PAGE |
| | 2. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | D)THERE IS NOT PTAC INSTALLED IN THIS HOUSE. REVISE |
| | INFORMATION SHOWN ON PAGE 2. SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E)WATER HEATER INFORMATION ON PAGE 2 DOESN'T MATCH |
| | PLANS. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |