2022-07-18 16:15:20FAILED
  
 1) THE INSTALLATION OF THE ABOVE GROUND EV
 INFRASTRUCTURE REQUIRES CHANGES TO THE SITE AND
 LANDSCAPE PLANS. THESE CHANGES REQUIRE THE APPROVAL OF
 A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE CURRENTLY
 APPROVED PLANS. PLEASE CONTACT ME FOR INFORMATION ON
 THE APPLICATION. THE MINOR PLANNED DEVELOPMENT
 AMENDMENT MUST BE APPROVED PRIOR TO THE ZONING APPROVAL
 OF THIS PERMIT.
  
 2) THE PROPOSED LOCATION OF THE EV CHARGERS, THE DC
 CHARGEBOX, THE UNDERGROUND ELECTRIC CONNECTIONS, ETC.
 DIRECTLY CONFLICT WITH EXISTING LANDSCAPE. THE PROPOSED
 INSTALLATION MUST BE OVERLAID ON THE APPROVED LANDSCAPE
 PLAN TO VERIFY THAT THERE ARE NO CONFLICTS. PLEASE NOTE
 THAT STAFF WILL NOT SUPPORT THE REMOVAL OF TREES FOR
 THE INSTALLATION OF THE EV INFRASTRUCTURE.
  
 3) THE DC CHARGEBOX IS MECHANICAL EQUIPMENT IS REQUIRED
 TO BE SCREENED.
  
 4) THE SPACES THAT ARE ADJACENT TO THE EV SPACES ARE
 CUSTOMER PARKING SPACES, TO YOU ARE REQUIRED TO PROVIDE
 EV TO AT LEAST ONE ADA PARKING SPACE.
  
 5) ADDITIONAL COMMENTS MAY BE ISSUED UPON REVIEW OF THE
 MINOR PLANNED DEVELOPMENT AMENDMENT APPLICATION.
  