Plan Review Notes
Plan Review Notes For Permit 22060227
Permit Number 22060227
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-09-02 12:25:20FIRE REVIEW COMMENTS:
  
 THE SUBMITTED PLAN WAS REVIEWED AND FAILED WITH THE
 FOLLOWING:
  
 (1) ALL SYSTEMS SHALL HAVE BOTH AUTOMATIC AND MANUAL
 METHODS OF ACTIVATION. NFPA 17A 5.2
  
 (2) PROVIDE THE DISTANCE BETWEEN THE HOOD AND THE
 MANUAL ACTIVATION, PATH OF EGRESS, AND THE MOUNTING
 HEIGHT OF THE MANUAL ACTIVATION. NFPA 96 10.5
  
 (3) PROVIDE INFORMATION ON FUSIBLE LINKS TO BE
 UTILIZED. NFPA 17A 4.4.1
  
 (4) PROVIDE THE DISTANCE OF THE COOKING APPLIANCES IN
 REGARDS TO THE HOOD PERIMETER. NFPA 17A 5.1.2
  
 (5) AN AUDIBLE OR VISUAL INDICATOR SHALL BE PROVIDED TO
 SHOW THAT THE SYSTEM HAS OPERATED. NFPA 17A 5.2.1.8
  
 (6) PROVIDE THE DISTANCE OF THE NOZZLES TO THE COOKING
 SURFACE. NFPA 17A 5.5
  
 (7) PROVIDE THE DISTANCE FROM THE COOKING SURFACE TO
 THE PORTABLE CLASS K FIRE EXTINGUISHER LOCATION. NFPA
 96.10.5.1.1
  
 WHEN RESUBMITTING, CORRECTIONS AND/OR ADDITIONS TO THE
 ORIGINAL PLAN SET SHALL BE CLOUDED OR IN A NARRATIVE
 EXPLANATION NOTE..
  