2022-08-11 13:25:152ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060206
 8/11/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. 2ND REQUEST FOR THE ITEMS
 #1-3 FROM THE 1ST REVIEW LISTED BELOW.
  
 1) SHEET 2: PROVIDE A POOL PIPING DIAGRAM THAT SHOWS
 THE POOL, SPA, AND FEATURE PRESSURE AND SUCTION PIPING,
 AND THE RECIRCULATION EQUIPMENT- PUMPS, FILTERS,
 CHEMICAL FEEDERS, VALVES AND HEATERS- SEC. 107.2.1 WPB.
 PLEASE INCLUDE THE PIPE SIZES AND THE VELOCITIES OF THE
 PIPING IN FPS- SEC. R4501.6.3 FBC RES.
  
 2) SHEET 2: PROVIDE POOL AND SPA SPECIFICATIONS
 INCLUDING THE SQUARE FOOT AREAS, VOLUME IN GALLONS,
 DESIGN FLOW RATES, SYSTEM FLOW RATES, AND THE TURNOVER
 RATE- SECS. R4501.6.1 FBC RES.
  
 3) SHEET 2: PROVIDE TDH CALCULATIONS, AND THE PUMP
 CURVE MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE
 SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  