| 2022-06-14 07:12:31 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22060206 |
| | 6/13/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2: PROVIDE A POOL PIPING AND EQUIPMENT |
| | ISOMETRIC DRAWING THAT SHOWS THE POOL, SPA, AND FEATURE |
| | PRESSURE AND SUCTION PIPING, AND THE RECIRCULATION |
| | EQUIPMENT- PUMPS, FILTERS, CHEMICAL FEEDERS, VALVES AND |
| | HEATERS- SEC. 107.2.1 WPB. PLEASE INCLUDE THE PIPE |
| | SIZES AND THE VELOCITIES OF THE PIPING IN FPS- SEC. |
| | R4501.6.3 FBC RES. |
| | |
| | 2) SHEET 2: PROVIDE POOL AND SPA SPECIFICATIONS |
| | INCLUDING THE POOL SIZE, DEPTH, AREA, VOLUME IN |
| | GALLONS, DESIGN FLOW RATE, SYSTEM FLOW RATE, AND THE |
| | POOL TURNOVER RATE- SECS. R4501.6.1 FBC RES. |
| | |
| | 3) SHEET 2: PROVIDE TDH CALCULATIONS, AND THE PUMP |
| | CURVE MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE |
| | SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & |
| | R4501.7.2 & R4501.7.3 FBC RES. |
| | |
| | 4) SHEET 2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE RECIRCULATION EQUIPMENT INCLUDING THE MAIN DRAIN |
| | COVERS, PUMPS, FILTER, AND THE PUMP CURVE FROM THE |
| | MANUFACTURER- SECS. R4501.6.2, R4501.6.6, R4501.7.2, |
| | R4501.20 & R4501.21.3 FBC RES. |
| | |
| | 5) SHEET 2: PLACE A NOTE INDICATING THE GAS POOL HEATER |
| | AND GAS PIPING WILL BE DONE UNDER A SEPARATE PERMIT- |
| | SEC. 105.1 & 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |