Plan Review Notes
Plan Review Notes For Permit 22060206
Permit Number 22060206
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-14 07:12:311ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060206
 6/13/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: PROVIDE A POOL PIPING AND EQUIPMENT
 ISOMETRIC DRAWING THAT SHOWS THE POOL, SPA, AND FEATURE
 PRESSURE AND SUCTION PIPING, AND THE RECIRCULATION
 EQUIPMENT- PUMPS, FILTERS, CHEMICAL FEEDERS, VALVES AND
 HEATERS- SEC. 107.2.1 WPB. PLEASE INCLUDE THE PIPE
 SIZES AND THE VELOCITIES OF THE PIPING IN FPS- SEC.
 R4501.6.3 FBC RES.
  
 2) SHEET 2: PROVIDE POOL AND SPA SPECIFICATIONS
 INCLUDING THE POOL SIZE, DEPTH, AREA, VOLUME IN
 GALLONS, DESIGN FLOW RATE, SYSTEM FLOW RATE, AND THE
 POOL TURNOVER RATE- SECS. R4501.6.1 FBC RES.
  
 3) SHEET 2: PROVIDE TDH CALCULATIONS, AND THE PUMP
 CURVE MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE
 SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES.
  
 4) SHEET 2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE RECIRCULATION EQUIPMENT INCLUDING THE MAIN DRAIN
 COVERS, PUMPS, FILTER, AND THE PUMP CURVE FROM THE
 MANUFACTURER- SECS. R4501.6.2, R4501.6.6, R4501.7.2,
 R4501.20 & R4501.21.3 FBC RES.
  
 5) SHEET 2: PLACE A NOTE INDICATING THE GAS POOL HEATER
 AND GAS PIPING WILL BE DONE UNDER A SEPARATE PERMIT-
 SEC. 105.1 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  