Plan Review Notes
Plan Review Notes For Permit 22060203
Permit Number 22060203
Review Stop E
Sequence Number 1
Notes
Date Text
2022-06-30 09:24:43FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GROUNDING ELECTRODE SYSTEM TO BE INSTALLED PER
 250.32(A) AT EACH BUILDING.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING
 ELECTRODE OR GROUNDING ELECTRODE SYSTEM INSTALLED IN
 ACCORDANCE WITH PART III OF ARTICLE 250. THE GROUNDING
 ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE,
 THE GROUNDING ELECTRODE(S) REQUIRED IN 250.50 SHALL BE
 INSTALLED.
  
 HAND DRYERS TO BE GFCI PROTECTED PER 210.8(B) WITHIN 6'
 OF A SINK.
  
 RECEPTACLE. A CONTACT DEVICE INSTALLED AT THE OUTLET
 FOR THE CONNECTION OF AN ATTACHMENT PLUG, OR FOR THE
 DIRECT CONNECTION
 OF ELECTRICAL UTILIZATION EQUIPMENT DESIGNED TO MATE
 WITH THE CORRESPONDING CONTACT DEVICE. A SINGLE
 RECEPTACLE IS A SINGLE
 CONTACT DEVICE WITH NO OTHER CONTACT DEVICE ON THE SAME
 YOKE A MULTIPLE RECEPTACLE IS TWO OR MORE CONTACT
 DEVICES ON THE
 SAME YOKE. (CMP-18)
  
  