| Date |
Text |
| 2022-06-03 12:42:52 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL10483-R27 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. |
| | 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| | TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY |
| | LIMITATIONS 5.6.1OF PRODUCT APPROVAL FL14083-R27. |
| | 3. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE |
| | REPORT PREPARED BY A FLORIDA REGISTERED DESIGN |
| | PROFESSIONAL. |
| | 4. FBC B 107.1 FS 481.229 ( C ) BUILDINGS INTENDED FOR |
| | PUBLIC USE; PLANS REQUIRE PREPARATION BY A REGISTERED |
| | DESIGN PROFESSIONAL. PROVIDE A COMPLETE SET FOR ROOF |
| | METAL RETROFITS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |