| Plan Review Notes For Permit 22060187 |
| Permit Number |
22060187 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-01 09:27:57 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS, | | | ROOFING SYSTEMS. | | | | | | 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB | | | 107.3.4 | | | | | | 3) PLEASE SHOW THE LANDING FOR THE SLIDING GLASS DOOR - | | | FBC R311.3.2 FLOOR ELEVATIONS FOR OTHER EXTERIOR DOORS. | | | DOORS OTHER THAN THE REQUIRED EGRESS DOOR SHALL BE | | | PROVIDED WITH LANDINGS OR FLOORS NOT MORE THAN 7 3/4 | | | INCHES (196 MM) BELOW THE TOP OF THE THRESHOLD. | | | | | | 4) DRAWING S-100 UNDER "STRUCTURAL NOTES" SHOW THE 2017 | | | FBC USED FOR DESIGN - SHOULD BE 2020 FBC | | | | | | 5) DRAWING S-102 - DETAIL NUMBER 4 - ROOF NAILING ZONE | | | DIAGRAM GIVES OPTIONS FOR PLYWOOD NAILING AND STATES | | | PLYWOOD CAN BE VERTICAL OR HORIZONTAL (THAT NOTE SHOULD | | | BE FOR WALL SHEATHING) - OTHER CUT SECTIONS CLEARLY | | | SHOW THE SIZE AND NAILING OF THE PLYWOOD - PERHAPS YOU | | | CAN REMOVE THE NAILING ZONE DIAGRAM DETAIL NUMBER 4. |
|