| Plan Review Notes For Permit 22060125 |
| Permit Number |
22060125 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-13 09:09:16 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE A CLEAR DETAILED | | | SPECIFICATION FOR THE TIE DOWN CONNECTIONS OF THE | | | MECHANICAL EQUIPMENT. THIS DETAIL NEEDS TO INCLUDE THE | | | DESIGN WINDLOADS AND SIGNED/SEALED BY ENGINEER. IF THIS | | | COMES IN THE FORM OF A PRODUCT APPROVAL, THE PRODUCT | | | APPROVAL MUST BE UP TO DATE. ALL PRODUCT APPROVALS | | | SUBMITTED MUST BE REVIEW STAMP APPROVED BY DESIGNER OF | | | RECORD. | | | |
|