| 2022-06-30 06:34:19 | BASED ON FMC 403.3.1.1 AND TABLE 403.3.1.1 THE SALES | | | AREA OF THIS TENANT SPACE WILL REQUIRE 173 CFM'S OF | | | OUTDOOR AIR AND THE STORAGE AREA WILL REQUIRE 98 CFM'S | | | OF AIR. HOW WILL THE DESIGN PRESENTED REMOVE THE | | | HUMIDITY IN THE OUTDOOR AIR SO THIS TENANT WILL NOT | | | HAVE TO BE CONCERNED ABOUT HUMIDITY? | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|