2022-06-30 06:34:19BASED ON FMC 403.3.1.1 AND TABLE 403.3.1.1 THE SALES
 AREA OF THIS TENANT SPACE WILL REQUIRE 173 CFM'S OF
 OUTDOOR AIR AND THE STORAGE AREA WILL REQUIRE 98 CFM'S
 OF AIR. HOW WILL THE DESIGN PRESENTED REMOVE THE
 HUMIDITY IN THE OUTDOOR AIR SO THIS TENANT WILL NOT
 HAVE TO BE CONCERNED ABOUT HUMIDITY?
  