| 2022-06-06 12:36:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT, BUT THE SPEC SHEET FOR THE ACTUAL |
| | PROPOSED LAMINATE FLOORING DOES NOT INDICATE A FLAME |
| | RATING. |
| | |
| | LMINATE FLOORING IS MANUFACTURED AROUND THE WORLD AND |
| | NOT ALL ARE TESTED AND MEETING LISTED AND NFPA |
| | STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| | SPEC SHEETS OF THE PROPOSED FINISHED |
| | LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | I CHECKED MY RESOURCES ONLINE AND COULD NOT FIND THE |
| | FLAME RATING FOR THIS PRODUCT. |
| | |
| | YOU MAY NEED TO CONTACT HOMEDEPOT TO REQUEST THE |
| | SPECFIC MANUFACTURER'S SPEC SHEET |
| | |
| | |
| | 2) A FLOOR PLAN WA NOT SUBMITTED TO SEPCIFICAALY |
| | INDICATE WHERE THE FLOORING WILL BE INSTALLED. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PALN |
| | INDICATING THE AREAS FOR THE PROPOSED FLOORING. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |