| Plan Review Notes For Permit 22051536 |
| Permit Number |
22051536 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-02 14:27:29 | FIRE COMMENTS: | | | A RECORD OF COMPLETION SHALL BE COMPLETED AND SUBMITTED | | | BY THE INSTALLING CONTRACTOR TO THE ENFORCING AUTHORITY | | | (WEST PALM BEACH FIRE DEPARTMENT) AT THE TIME OF FINAL | | | INSPECTION. | | | A TEST OF THE SECONDARY POWER SUPPLY PER NFPA 72, SHALL | | | BE WITNESSED BY THE FIRE DEPARTMENT. | | | RECOMMEND ADDING A SMOKE DETECTOR TO STORAGE ROOM 157, | | | SIMILAR TO STORAGE ROOM 146 AND PANTRY ROOM 110, FOR | | | SYSTEM INSTALLATION CONGRUENCE. | | | |
|