| Plan Review Notes For Permit 22051488 |
| Permit Number |
22051488 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-25 07:02:53 | 1) SHEET M101: THE NOTE FOR THE LAUNDRY ROOM IS CALLING | | | FOR MAKE UP AIR BUT EF-4 IS AN EXHAUST FAN WHICH | | | REMOVES AIR FROM THE ROOM. PROVIDE A DESIGN FOR THE | | | MAKE UP AIR IF REQUIRED FOR THIS SPACE AND REMOVE THE | | | EXHAUST FAN. FBC 107.3.5 | | | | | | 2) AGAIN, PLEASE PROVIDE THE DUCT SIZES FOR THE NEW | | | DUCTWORK. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|