Plan Review Notes
Plan Review Notes For Permit 22051488
Permit Number 22051488
Review Stop R
Sequence Number 2
Notes
Date Text
2022-08-16 08:45:51PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW DENIED:
  
 FBC R 905.3, IN ACCORDANCE WITH NOA 17-0727.07 & THE
 FRSA/TRI CONCRETE & CLAY TILE INSTALLATION GUIDE,
 PLEASE IDENTIFY THE OPTION OF UNDERLAYMENT THAT WILL BE
 USED (EXAMPLE: HOT MOP/SELF ADHERING). ALSO, IDENTIFY
 THE METHOD OF ROOF TILE ANCHORING (EXAMPLE: MECHANICAL
 FASTENING/FOAM ADHESIVE). THE METHODS CHOSEN MUST MEET
 THE WIND LOAD REQUIREMENTS AS PER THE NOTED CODE
 REQUIREMENTS.
  
 NOTE: A ROOFING SUB-PERMIT IS REQUIRED.