2022-07-11 12:14:11PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN. IS
 THE AHU BEING CHANGED OUT OR IS IT EXISTING TO STAY? IS
 THIS MECHANICAL DESIGN USING AN ABOVE CEILING PLENUM
 FOR THE RETURN? I SEE RETURN REGISTERS BUT NO DUCT
 WORK. PROVIDE A COMPLETE MECHANICAL DRAWING SHOWING THE
 RETURN DUCT WORK AND THE RETURNS FROM ALL ROOMS WITH
 DOORS. FBC 107.2.1
  
  