| Plan Review Notes For Permit 22051488 |
| Permit Number |
22051488 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-11 12:14:11 | PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN. IS | | | THE AHU BEING CHANGED OUT OR IS IT EXISTING TO STAY? IS | | | THIS MECHANICAL DESIGN USING AN ABOVE CEILING PLENUM | | | FOR THE RETURN? I SEE RETURN REGISTERS BUT NO DUCT | | | WORK. PROVIDE A COMPLETE MECHANICAL DRAWING SHOWING THE | | | RETURN DUCT WORK AND THE RETURNS FROM ALL ROOMS WITH | | | DOORS. FBC 107.2.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|